Gürsel Günacar (@dev_mep)

Gürsel Günacar @dev_mep 2026-11-17T19:16:44.000Z

Built an interactive 3D + 2D Boiler Room & Hydraulic Separator simulator with Gemini Argon. What happens when secondary zone pumps run on a common manifold without a low-loss header? The high-head AHU pump (-30.7 kPa) starves the radiators and pulls water backwards out of Zone 3.

0 0 67 2 0
Gürsel Günacar @dev_mep 2026-11-17T19:17:04.000Z

It also solves the 3 thermal regimes of a hydraulic separator: 1. Qp = Qs: Balanced 70/52.5°C — boiler condenses (<54°C dew point) 2. Qp > Qs: Hot downward bypass pushes return to 58.1°C — kills condensation 3. Qp < Qs: Cool return recirculates up — drops building supply to 58.9°C

0 0 8 0 0
Gürsel Günacar @dev_mep 2026-11-17T19:16:53.000Z

What the model analyzes in real time: • Direct-coupled manifold conflict: pump starvation (Z1 drops to 56%) & reverse circulation in low-head zones (Z3 at -0.68 m³/h) • Caleffi 3D sizing rule (D = 3d): 9× area expansion drops velocity to 0.10 m/s (≤ 0.15 m/s limit) for air & dirt separation

0 0 25 0 0
Avenox @Avenoxai 2026-11-15T15:47:41.000Z

Şu OpenBot'u o kadar sordunuz ki, bir kurcalıyorum. Genel olarak tasarımına aşık oldum, ama Hermes'ten buraya geçmek için net bir sebebim yok şu anlık.

134 4 18195 16 0